BIRLA CABLE LTD.
Easy Responsive Tabs to Accordion

  • FIBRE OPTIC CABLES
  • TELECOM FIBRE ACCESSORIES
  • STRUCTURED CABLES
  • STRUCTURED CABLE ACCESSORIES

  • AERIAL
  • UNDERGROUND DUCT
  • MICRODUCT
  • MICROMODULE
  • FTTX
  • SPECIALITY
  • INDOOR

STRUCTURED CABLES > CAT6A

4 PAIR CAT 6A 23AWG UTP CABLE

Ipsum

Typical Cross section

Electrical Characteristics:

Conductor Resistance@20°C Max. 9.38 Ω/100m
Conductor Resistance Unbalance Max. 5 %
Mutual Capacitance Max. 5.6 nF/KM
Capacitance Earth Unbalance Max. 330 pF/100m
Insulation Resistance Min. 5000 M.Ohm km
Dielectric Strength DC 2500V/2s
Propagation Delay @ 1 , 10 , 100 & 500 MHz Max. 570, 545, 538 & 536 ns/100 m
Velocity of Propagation 69%(nom)
Propagation DeLay Skew 1 –500 MHz Max. 45 ns/100 m

Description:

Conductor : 23AWG Solid Annealed Bare Copper Conductor
Insulation : High Density Polyethylene
Pair Screening : Two Insulated conductors Twisted together to form pair ,lay ≤ 30mm
Twisting : 4 pairs laid together and separated by cross element
Sheath : PVC/LSZH, inside corrugated Jacket
Colour : Grey or as per request.
Cable Diameter : 7.2 ± 0.4 mm

Features:

  • Reference standard TIA/EIA 568 C.2 (Category 6a) & ISO/IEC 11801 2nd ed(Class Ea)
  • Packaged in Wooden Spoo
  • True 23 AWG Solid Bare Copper
  • 305 Meters Reel. 500 Meters Reel in Option
  • Channel” Performance Warranty

Technical Details

Freq (MHZ) Attenuation (dB/100m) NEXT (dB) PSNEXT (dB) ACRF (ELFEXT)(dB) PSACRF [PSELFEXT] (dB) Return Loss
(dB)
Max. Min. Min. Min. Min. Min.
1 2.3 65 62 63.3 60.3 19
4 4.2 63 60.5 51.2 48.2 19
8 5.8 58.2 55.6 45.2 42.2 19
10 6.5 56.6 54 43.3 40.3 19
16 8.2 53.2 50.6 39.2 36.2 18
20 9.2 51.6 49 37.2 34.2 17.5
25 10.2 50 47.3 35.3 32.3 17
31.25 11.5 48.4 45.7 33.4 30.4 16.5
62.5 16.4 43.4 40.6 27.3 24.3 14
100 20.9 39.9 37.1 23.3 20.3 12
200 30.1 34.8 31.9 17.2 14.2 9
250 33.9 33.1 30.2 15.3 12.3 8
300 37.4 31.7 28.8 13.7 10.7 7.2
400 43.7 28.7 25.8 11.2 8.2 6
500 49.3 26.1 23.2 9.3 6.3 6

Note:

Supplied cable shall be passed Fluke Channel Test as per ANSI/TIA 568-C.2

Colour Code:

Pair 1 : White/Blue Strip -Blue
Pair 2 : White/Orange Strip -Orange
Pair 3 : White/Green Strip-Green
Pair 4 : White/Brown Strip-Brown

Standard Length & Packing:

305m Spool Dimension (FxBxT) : 14 x 6 x 12 Inch

Mechanical Properties:

Bending radius : 8 x overall diameter (min.)
Breaking strength : 400 N (max.)

Thermal Characteristics:

Operating Temperature : - 20°C to +60°C
Installation Temperature : -0°C to +50°C
Flammability : IEC 60332-1-2